You signed in with another tab or window. Reload to refresh your session.You signed out in another tab or window. Reload to refresh your session.You switched accounts on another tab or window. Reload to refresh your session.Dismiss alert
I am trying to communicate with my SDM120-modbus. I am pretty sure I have wired everything correctly (B to 9 and A to 10), but somehow I cannot talk to the SDM120. This is the output I am getting:
ubuntu@ubuntu:~/smartmeter$ SDM120C/sdm120c -a 1 -b 9600 -e -p -q -z 3 -j 20 -d 1 /dev/ttyUSB2
20210123-20:23:38.858984: SDM120C/sdm120c(32257) debug_flag = 1
20210123-20:23:38.859152: SDM120C/sdm120c(32257) cmdline="SDM120C/sdm120c -a 1 -b 9600 -e -p -q -z 3 -j 20 -d 1 /dev/ttyUSB2"
20210123-20:23:38.859270: SDM120C/sdm120c(32257) szttyDevice: /dev/ttyUSB2
20210123-20:23:38.859373: SDM120C/sdm120c(32257) devLCKfile: </var/lock/LCK..ttyUSB2>
20210123-20:23:38.859472: SDM120C/sdm120c(32257) devLCKfileNew: </var/lock/LCK..ttyUSB2.32257>
20210123-20:23:38.859572: SDM120C/sdm120c(32257) PID: 32257
20210123-20:23:38.859781: SDM120C/sdm120c(32257) Attempting to get lock on Serial Port /dev/ttyUSB2...
20210123-20:23:38.859944: SDM120C/sdm120c(32257) Acquiring shared lock on /var/lock/LCK..ttyUSB2...
20210123-20:23:38.860058: SDM120C/sdm120c(32257) Shared lock on /var/lock/LCK..ttyUSB2 acquired...
20210123-20:23:38.860308: SDM120C/sdm120c(32257) Checking for lock
20210123-20:23:38.860536: SDM120C/sdm120c(32257) errno=0, bRead=2 PID=32257 LckPID=32257
20210123-20:23:38.860704: SDM120C/sdm120c(32257) Checking process 32257 (SDM120C/sdm120c) for lock
20210123-20:23:38.860906: SDM120C/sdm120c(32257) PID: 32257 COMMAND: "SDM120C/sdm120c" LckPID: 32257 LckCOMMAND: "SDM120C/sdm120c" LckPIDcommand "SDM120C/sdm120c" = me
20210123-20:23:38.861006: SDM120C/sdm120c(32257) Appears we got the lock.
20210123-20:23:38.861103: SDM120C/sdm120c(32257) resp_timeout=2000000us
20210123-20:23:38.861209: SDM120C/sdm120c(32257) Libmodbus context open (9600E1)
20210123-20:23:38.861311: SDM120C/sdm120c(32257) Byte timeout disabled.
20210123-20:23:38.861413: SDM120C/sdm120c(32257) New response timeout: 0s, 2000000us
20210123-20:23:38.865284: SDM120C/sdm120c(32257) 1/3. Register Address 30013 [000C]
20210123-20:23:39.366133: SDM120C/sdm120c(32257) ERROR (110) Connection timed out, 1/3, Address 30013 [000C]
20210123-20:23:39.366340: SDM120C/sdm120c(32257) Response timeout gave up after 500634us
20210123-20:23:39.366485: SDM120C/sdm120c(32257) 2/3. Register Address 30013 [000C]
20210123-20:23:39.867357: SDM120C/sdm120c(32257) ERROR (110) Connection timed out, 2/3, Address 30013 [000C]
20210123-20:23:39.867538: SDM120C/sdm120c(32257) Response timeout gave up after 500668us
20210123-20:23:39.867682: SDM120C/sdm120c(32257) 3/3. Register Address 30013 [000C]
20210123-20:23:40.368541: SDM120C/sdm120c(32257) ERROR (110) Connection timed out, 3/3, Address 30013 [000C]
20210123-20:23:40.368763: SDM120C/sdm120c(32257) Response timeout gave up after 500658us
20210123-20:23:40.370568: SDM120C/sdm120c(32257) devLCKfile: </var/lock/LCK..ttyUSB2>
20210123-20:23:40.370722: SDM120C/sdm120c(32257) devLCKfileNew: </var/lock/LCK..ttyUSB2.32257>
20210123-20:23:40.370848: SDM120C/sdm120c(32257) Clearing Serial Port Lock (32257)...
20210123-20:23:40.371056: SDM120C/sdm120c(32257) Acquiring exclusive lock on /var/lock/LCK..ttyUSB2...
20210123-20:23:40.371282: SDM120C/sdm120c(32257) Exclusive lock on /var/lock/LCK..ttyUSB2 acquired (0) Success...
20210123-20:23:40.371573: SDM120C/sdm120c(32257) cmdLen=15
20210123-20:23:40.371711: SDM120C/sdm120c(32257) cmdLen=15 COMMAND is not null
20210123-20:23:40.371940: SDM120C/sdm120c(32257) errno=0, bRead=2 LckPID=32257 PID=32257 COMMAND='SDM120C/sdm120c'
20210123-20:23:40.372080: SDM120C/sdm120c(32257) errno=0, bRead=-1 LckPID=32257 PID=0 COMMAND=''
20210123-20:23:40.372391: SDM120C/sdm120c(32257) Clearing Serial Port Lock done
NOK
20210123-20:23:40.372705: SDM120C/sdm120c(32257) NOK
The USB-modbus-RS485 device is located on /dev/ttyUSB2 (I checked this with dmesg). Any help would be appreciated!
The text was updated successfully, but these errors were encountered:
I have been fiddling a bit more, and after swapping some USB-connections on the Raspberry Pi I seem to be able to retrieve some data from the SDM120:
ubuntu@ubuntu:~/smartmeter$ SDM120C/sdm120c /dev/ttyUSB0 -P N
Voltage: 235.30 V
Current: 0.31 A
Power: 0.00 W
Active Apparent Power: 70.59 VA
Reactive Apparent Power: -70.51 VAR
Power Factor: -0.05
Phase Angle: 0.00 Degree
Frequency: 50.00 Hz
Import Active Energy: 6576848 Wh
Export Active Energy: 0 Wh
Total Active Energy: 6576848 Wh
Import Reactive Energy: 1974940 VARh
Export Reactive Energy: 1492504 VARh
Total Reactive Energy: 3467444 VARh
OK
But when I change the baud rate (from the default 2400) it errors in NOK. Any idea why this happens?
Hello, have you changed default speed from 2400 to 9600 using parametr -r, after putting meter in programming mode (push front button for 3 sec).
If not, this is the cause
I am trying to communicate with my SDM120-modbus. I am pretty sure I have wired everything correctly (B to 9 and A to 10), but somehow I cannot talk to the SDM120. This is the output I am getting:
The USB-modbus-RS485 device is located on /dev/ttyUSB2 (I checked this with dmesg). Any help would be appreciated!